125-250A VKA load break switches, compact in size, 3 and 4 pole available as a standard. 2, 6 and 8 pole VKA versions are available upon request. With switch technology, the silver contact ensures safe and durable operations. Tested according to IEC 60269. Certificates - CE, RINA, RoHS, GostR, KEMA and EAC.
| Type | AC-22 | 400 V | AC-23 | AC-23 | EAN-Code | ||
| 415 V | 400 V | 690 V | |||||
| 690 V | 415 V | ||||||
| Model | Ie / A | Ie / A | Ie / A | ||||
| 3-pole | |||||||
| VKA 3125N | 125 A | 80 A | 45 kW | 80 A | 55 kW | 6419410217504 | |
| VKA 3160N | 160 A | 135 A | 75 kW | 125 A | 90 kW | 6419410218006 | |
| 4-pole | |||||||
| VKA 4125N | 125 A | 80 A | 45 kW | 80 A | 55 Kw | 6419410218600 | |
| VKA 4160N | 160 A | 135 A | 75 kW | 125 A | 90 kW | 6419410219102 | |
| Type | AC-21 | AC-21 | AC-22 | AC-23 | EAN-Code | ||||
| 400 V | 690 V | 400 V | 400 V | ||||||
| 415 V | 415 V | 415 V | |||||||
| Model | Ie / A | Ie / A | Ie / A | Ie / A | |||||
| 3-pole | |||||||||
| VKA 3200 | 200 A | 200 A | 200 A | 200 A | 110 kW | 6419410218020 | |||
| VKA 3250 | 250 A | 250 A | 250 A | 250 A | 132 kW | 6419410218044 | |||
| VKA 3200 LS/VS | 200 A | 200 A | 200 A | 200 A | 110 kW | 6419410218037 | |||
| VKA 3250 LS/VS | 250 A | 250 A | 250 A | 250 A | 132 kW | 6419410218051 | |||
| 4-pole | |||||||||
| VKA 4200 | 200 A | 200 A | 200 A | 200 A | 110 kW | 6419410219126 | |||
| VKA 4250 | 250 A | 250 A | 250 A | 250 A | 132 kW | 6419410219140 | |||
| VKA 4200 LS/VS | 200 A | 200 A | 200 A | 200 A | 110 kW | 6419410219133 | |||
| VKA 4250 LS/VS | 250 A | 250 A | 250 A | 250 A | 132 kW | 6419410219157 | |||
Compact size
3-pole and 4-pole VKA-switches as standard
2-pole upon request
4-pole versions with early-make and late-break neutral pole
125-160A: 6-pole and 8-pole versions consist of two 3-pole or 4-pole VKA-switches connected by a parallel kit
Compatible with handles LK10 and LK11
Shafts L=100/200 AD11 and L=100/200/300 AD11/VT
200-250A: Handle LK12 and shaft L=228 AD12/T6 included, suitable for 250 mm panel board
Terminal covers LS/VKAC and phase barriers VS/VKAC enable safe use
Tested according to IEC 60947-3